Switch Mode Power Supply, Capacity 300 W, Output voltage 48 V, Covered type, DIN track mounting
Power rating | 300 W |
---|---|
Output voltage | 48 VDC |
Rated input voltage | 100 to 240 VAC |
Construction | Covered type |
Connection | Terminal blocks |
Terminal type | Screw terminal |
As of July 25, 2024
Power rating | 300 W | |
---|---|---|
Output voltage | 48 VDC | |
Efficiency | 78 % min. | |
Input | Rated input voltage | 100 to 240 VAC |
Allowable input voltage variable range | 85 to 264 VAC 80 to 370 VDC | |
Frequency | 50/60Hz (47 to 63 Hz) | |
Rated input current | 4.5 A max. (at 100 VAC input) 2.2 A max. (at 200 VAC input) | |
Power factor | 0.9 min. | |
Leakage current | 0.5 mA max. (at 100 VAC input) 1 mA max. (at 200 VAC input) | |
Inrush current (cold start at 25 ℃) | 17.5 A max. (at 100 VAC input) 35 A max. (at 200 VAC input) | |
Output | Rated output current | 7 A |
Output voltage variable range | ±10 % (With V.ADJ) | |
Ripple | 2 %(p-p) max. | |
Static load variation influence | 0.8 % max. (at rated input, 0 to 100% load) | |
Ambient temperature variation influence | 0.05 %/℃ max. | |
Start up time | 1000 ms max. | |
Hold time | 20 ms min. (at 100 VAC input) (at 100% load) 20 ms min. (at 200 VAC input) | |
Additional functions | Overload protection | Yes, automatic reset |
Overvoltage protection | Yes, Shut off the input voltage and turn on the input again | |
Overheat protection | Yes, Shut off the input voltage and turn on the input again | |
Series operation | Yes (Up to 2 Power Supplies with external diode) | |
Parallel operation | Yes (Up to 5 Power Supplies) | |
Alarm indication | Yes (color: red) | |
Output indicator | Yes (color: green) | |
Remote sensing function | Yes | |
Remote control function | Yes | |
Insulation | Dielectric strength | Between all input terminals and all output terminals: 3 kVAC for 1 min, Detection current: 20 mA Between all input terminals and PE terminals: 2 kVAC for 1 min, Detection current: 20 mA Between all output terminals and PE terminals: 1 kVAC for 1 min, Detection current: 100 mA Between all output terminals and RC terminals: 100 VAC for 1 min, Detection current: 100 mA Between all output terminals and ALM terminals: 500 VAC for 1 min, Detection current: 20 mA |
Insulation resistance | Between all output terminals and all input terminals/ PE terminals: 100 MΩ min., at 500 VDC | |
Environment | Vibration resistance | 10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours |
Shock resistance | 150 m/s2, in each 6 directions 3 times | |
Ambient temperature (Operating) | -10 to 70 ℃ (with no freezing or condensation) | |
Ambient temperature (Storage) | -25 to 75 ℃ (with no freezing or condensation) | |
Ambient humidity (Operating) | 25 to 85 % | |
Ambient humidity (Storage) | 25 to 90 % | |
Construction | Construction | Covered type |
Connection | Terminal blocks | |
Terminal type | Screw terminal | |
Mounting | DIN track mounting | |
Cooling fan | Cooling fan Yes |
Note
Do not use the Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning.